Gauge, Transducer, Transmitter Or Switch: Which Does Your System Need?
A gauge shows pressure to a person, a transducer or transmitter sends it to a controller, and a switch acts when pressure crosses a set point.
This guide explains the differences with real numbers: what each one outputs, how a 4-20 mA signal works, what deadband means on a switch, and how to read an accuracy spec before you buy.
What Is The Difference Between A Pressure Gauge, Transducer, Transmitter And Switch?
Pressure gauge: shows the pressure locally on a dial or display for someone to read. Mechanical gauges need no power and send no signal.
Pressure transducer: converts pressure into an electrical signal. By the usual convention that is a small millivolt output that needs amplifying, though some products sold as transducers give 4-20 mA.
Pressure transmitter: a transducer with built-in electronics that sends a strong, standard signal (usually 4-20 mA or 0-10 V) over longer cable runs to a PLC, data logger or control system.
Pressure switch: does not report a value at all. It opens or closes an electrical contact when pressure rises above or falls below a set point, to start a pump, trip an alarm or shut a process down.
Gauge vs Transducer vs Transmitter vs Switch Compared
If you only read one thing, read this table. It compares the four devices on what they output, what they need and where each one fits.
Naming note: these are the common conventions, but manufacturers use "transducer" and "transmitter" differently. Always check the specified output on the datasheet.
| Pressure Gauge | Pressure Transducer | Pressure Transmitter | Pressure Switch | |
|---|---|---|---|---|
| What It Tells You | The pressure value, to a person | The pressure value, as a raw signal | The pressure value, as a standard signal | Only above or below a set point |
| Output | Needle or digital display | Commonly millivolts (mV/V), unamplified | 4-20 mA, 0-10 V, 1-5 V or digital | Contact opens or closes (NO, NC, SPDT) |
| Needs Power? | Mechanical: no. Digital: usually battery | Yes, an excitation voltage | Yes, usually loop or DC supply | Mechanical: no. Electronic: yes |
| Signal Distance | None, read at the point of use | Short, low-level signal picks up noise | Long runs; 4-20 mA handles them best | Long, it is just on/off |
| Typical Use | Local checks, test points, visual backup | Test rigs and OEM boards with their own amplifier | Process control, monitoring, data logging | Pump control, alarms, safety shutdowns |
| Example On This Page | Ashcroft digital gauge | See the naming note below | WIKA A-10 | Ashcroft watertight switch |
How Does A Pressure Gauge Work?
Most mechanical gauges use a Bourdon tube: a curved, flattened metal tube that tries to straighten as pressure inside it rises. A small gear movement turns that motion into needle travel across the dial. Low-pressure gauges use a diaphragm or capsule instead, because a Bourdon tube is not sensitive enough below a few psi.
A digital pressure gauge swaps the tube for an electronic sensor and a display. You get easier reading, unit switching, min/max memory and often better accuracy, A basic standalone digital gauge runs on a battery and does not send a signal anywhere. Some models add external power, an analogue output or switch contacts, which moves them closer to a transmitter or switch, so check the datasheet if you need that.
Gauges are the right answer when a person needs to see pressure at the point of use: on a gas regulator, a pump outlet, a hydraulic test port or a vacuum line. They are also the backup reading many sites keep next to a transmitter. For reading gauges in different units, see our kPa to psi converter and chart.
Industrial Pressure Gauge, 0 to 300 psi
- •±0.5% full-scale accuracy (ASME B40.1 grade 2A)
- •Stainless steel rotary gear movement
- •Heavy-gauge aluminium case
- •Supplied with a NIST-traceable calibration report from the manufacturer
Pressure Sensor vs Transducer vs Transmitter
These three words get used interchangeably, by suppliers as well as buyers, which is why search results disagree with each other. The most widely used convention is:
Pressure sensor: the sensing element itself, such as a strain gauge, piezoresistive silicon chip, thin-film or capacitive cell, whose electrical properties change with pressure. In everyday use, "pressure sensor" is also the umbrella term for all of the electronic devices below.
Pressure transducer: the sensor packaged with a pressure port and wiring, giving a millivolt output proportional to its excitation voltage (written mV/V). The signal is small, so it suits short cable runs into an amplifier, a test rig or an OEM board.
Pressure transmitter: a transducer with on-board signal conditioning that outputs an amplified voltage (0-5 V, 0-10 V, 1-5 V) or a 4-20 mA current. This is what most process control, building management and data logging systems expect.
Some manufacturers still call 4-20 mA devices "transducers". The Ashcroft K1 pressure transducer is a good example: it is sold as a transducer, yet its 4-20 mA output and 10 to 36 VDC supply make it a transmitter by the convention above. The practical rule is to choose by the output signal on the datasheet, not by the product name.
Quick check: if the output is written in mV or mV/V, plan for an amplifier or a meter with a strain-gauge input. If it is 4-20 mA or 0-10 V, it can usually go to a standard analogue input, as long as the input type (current or voltage), supply voltage and wiring match.
How A 4-20 mA Pressure Transmitter Works
A 4-20 mA transmitter controls the current flowing around a loop: 4 mA at the bottom of its range, 20 mA at the top, and a straight line in between. For a range that starts at zero, the formula is:
Current (mA) = 4 + 16 × (pressure ÷ full scale)
For any range, including compound and offset ranges, use the lower and upper range values:
Current (mA) = 4 + 16 × (pressure − lower range value) ÷ (upper range value − lower range value)
So on a 20 to 120 psi transmitter, 70 psi gives 4 + 16 × 50 ÷ 100 = 12 mA.
For a 0 to 100 psi transmitter such as the WIKA A-10, that gives the values below. The last column is the voltage you would read across a 250 Ω resistor in the loop, a common way to feed a 1-5 V input.
| Pressure | % Of Range | Loop Current | Across 250 Ω |
|---|---|---|---|
| 0 psi (0 kPa) | 0% | 4 mA | 1 V |
| 25 psi (172 kPa) | 25% | 8 mA | 2 V |
| 50 psi (345 kPa) | 50% | 12 mA | 3 V |
| 75 psi (517 kPa) | 75% | 16 mA | 4 V |
| 100 psi (689 kPa) | 100% | 20 mA | 5 V |
Working backwards is just as easy: a reading of 8.8 mA on that transmitter means (8.8 − 4) ÷ 16 × 100 = 30 psi (207 kPa).
Why Start At 4 mA, Not 0?
This is called a "live zero". Zero pressure still sends 4 mA, so a reading of 0 mA can only mean a fault: a broken wire, a lost power supply or a failed transmitter. A 0-10 V signal cannot tell a dead sensor from zero pressure.
Why Current Travels Further Than Voltage
In a series loop the same current flows through every part of the circuit, so resistance in long cables does not change the reading, as long as the supply has enough voltage to drive the loop. Current signals are also less affected by electrical noise than small voltages.
2-Wire Loop Wiring
Most 4-20 mA pressure transmitters are 2-wire (loop-powered): the same two wires carry the power and the signal. A DC supply, the transmitter and the receiving input are wired in series. Always check the supply range on the datasheet; the Ashcroft K1, for example, needs 10 to 36 VDC.
How Does A Pressure Switch Work?
Inside a mechanical pressure switch, pressure acts on a diaphragm, piston or bellows working against an adjustable spring. When the pressure force beats the spring, the element moves and snaps a microswitch over. Electronic switches use a pressure sensor and a solid-state or relay output instead, often with a display.
Set point: the pressure where the switch changes state, specified as rising (increasing) or falling (decreasing) pressure.
Deadband (reset differential): the gap between the trip point and the reset point. A switch set to trip at 80 psi (552 kPa) on rising pressure with a 10 psi deadband will not reset until pressure falls back to 70 psi (483 kPa). Without that gap the contact would chatter on and off whenever pressure hovered near the set point, wearing out the switch and whatever it controls.
Contacts: normally open (NO) contacts close when the switch trips; normally closed (NC) contacts open. "Normal" means the state at rest, with no pressure applied. An SPDT (single-pole, double-throw) switch gives you both, so you can wire either function.
Typical jobs: controlling when a pump or compressor starts and stops (through suitably rated control equipment such as a contactor or motor starter), low-pressure alarms on gas supplies, high-pressure cut-outs, and confirming airflow across a filter or fan. On low-pressure air systems, an explosion-proof switch rated to 10 inWC (about 2,491 Pa, or 24.9 mbar) shows how small these set points can be.
Fail-safe tip: wire alarms and shutdowns so the safe state is reached if a wire breaks. Many engineers use a contact that opens on the fault condition for this reason, then confirm the logic against the site's safety requirements.
Gauge, Sealed, Absolute And Differential Pressure
Every gauge, transducer, transmitter and switch measures pressure against something. Ordering the wrong reference is one of the most common specification mistakes.
| Reference | Measured Against | Reads Zero When | Typical Uses |
|---|---|---|---|
| Gauge (psig, kPa g) | The surrounding atmosphere, vented through the device | Open to air | Compressed air, water, hydraulics, most process lines |
| Sealed Gauge | A fixed reference sealed inside the device | At the pressure it was sealed at | Wet or dirty locations where a vent could let water in; high ranges |
| Absolute (psia, kPa a) | A perfect vacuum | In a perfect vacuum | Vacuum ovens, freeze dryers, barometric and altitude-sensitive work |
| Differential (psid) | A second pressure port | Both ports see the same pressure | Filters, cleanrooms, fume hoods, flow and tank level |
For the maths between gauge and absolute readings, see psig vs psia in our pressure conversion guide.
Differential Pressure Gauges, Transmitters And Switches
A differential pressure (DP) device has two ports and measures the difference between them. All four device types come in differential versions, and they do jobs a single-port instrument cannot:
- •Filter loading: pressure drop across a filter rises as it clogs, so a DP gauge or switch tells you when to change it.
- •Cleanrooms and labs: room-to-corridor pressure, often only a few pascals, keeps contamination flowing the right way.
- •Fume hoods and ducts: static and velocity pressure confirm extraction is working.
- •Flow: the pressure drop across an orifice plate or pitot tube is used to calculate flow rate.
- •Tank level: the difference between the bottom of a tank and the space above the liquid gives the liquid height.
Low differential ranges are usually quoted in inches of water column. The Ashcroft low differential pressure transmitter has a 15 inWC range, which is about 3,736 Pa (37.4 mbar), and its display can switch between inWC, Pa and mbar. For higher differentials the Ashcroft 2½" differential gauge reads 0 to 15 psid with no power at all; at ±2% of full scale that is ±0.3 psid.
For very low differentials and portable checks, a manometer is often the better tool. See our guide to manometer types and how to read one.
Pressure Accuracy Explained: Why % Of Full Scale Matters
Accuracy specs vary: some are a percentage of the reading, some combine several terms (non-linearity, hysteresis, temperature effects), and many gauges, transducers and transmitters quote a single figure as a percentage of full scale (FS) or span. With a %FS spec, the possible error is the same size anywhere on the range, so it is a bigger share of small readings.
As an example of how a %FS spec works, take two transmitters with the same ±0.5% FS rating, both reading 50 psi (345 kPa):
| Range | Accuracy | Possible Error | Error At 50 psi |
|---|---|---|---|
| 0 to 100 psi | ±0.5% FS | ±0.5 psi | 1% of the reading |
| 0 to 500 psi | ±0.5% FS | ±2.5 psi | 5% of the reading |
The same applies to gauges. A ±0.5% FS gauge with a 0 to 300 psi range can be out by ±1.5 psi. At 250 psi that is 0.6% of the reading; at 30 psi it is 5%.
Rule of thumb: pick a range that puts your normal operating pressure around the middle of the scale, with pressure peaks still inside it. Too small a range risks overpressure damage; too large a range throws away accuracy.
Which Pressure Device Do You Need?
Choose A Pressure Gauge If
- •Someone needs to read pressure at the equipment
- •There is no power or control system at that point
- •You want a simple visual backup to a transmitter
- •Cost and simplicity matter most
Choose A Transducer (mV Output) If
- •Your data acquisition system, amplifier or meter accepts a strain-gauge (mV/V) input
- •Cable runs are short and in a low-noise area
- •You are building a test rig or an OEM product with its own electronics
- •You want the fastest raw signal, with conditioning done downstream
Choose A Transmitter If
- •A PLC, BMS or data logger needs the pressure value
- •You need trends, records or remote monitoring
- •The signal has to travel more than a few metres
- •You want 4-20 mA fault detection (live zero)
Choose A Pressure Switch If
- •You only need an action at one pressure, not a value
- •You need to control when a pump or compressor runs
- •You need a simple alarm or safety cut-out
- •You want a control that works without a PLC
Specs To Check On Any Of Them
- •Range and reference (gauge, absolute, differential)
- •How accuracy is specified, and the overpressure rating
- •Wetted materials vs your gas or liquid
- •Process connection (NPT or BSP) and electrical connector
- •Ingress rating, temperature range and hazardous-area approvals
How They Work Together On One Pump Line
These devices are often used side by side rather than instead of each other. On a typical pump discharge line:
- •A pressure gauge lets the operator check pressure locally, and still reads if the power or control system is down.
- •A pressure transmitter sends the pressure value to the PLC for control, trending and alarms.
- •A separate pressure switch provides an independent high-pressure trip that does not rely on the PLC logic.
A transducer fits a different setup: a test rig or OEM machine whose data acquisition system already accepts its millivolt output. Choosing well usually means deciding which of these jobs each point in the system needs, then picking one device per job.
Where Each Device Is Used In Labs And Industry
Vacuum Ovens And Freeze Dryers
Absolute-reference transmitters and vacuum gauges confirm chamber pressure, because a gauge-reference reading changes with the weather.
Hydraulic Test Rigs
Fast-response transducers capture pressure spikes that a needle cannot follow, while a gauge on the rig gives the operator a live reading.
Pumps And Compressors
Pressure switches control motor starting and stopping through suitably rated control equipment and provide high-pressure cut-outs; a gauge on the outlet shows it is working.
Cleanrooms And Fume Hoods
Low differential transmitters feed the building management system, and differential switches trigger local alarms if airflow fails.
Gas Supply Lines
Gauges on regulators show cylinder and line pressure; low-pressure switches warn before a cylinder runs out.
Process And Water Systems
4-20 mA transmitters report line pressure and tank level to the control system over long cable runs.
Pressure Gauges, Transmitters And Switches At John Morris Group
One or two examples of each device type, from digital gauges to loop-powered transmitters, hazardous-area switches and low differential instruments. Browse the full ranges in pressure sensors and pressure transmitters.
Ashcroft Digital Pressure Gauge, 0 to 200 psi
A battery-powered digital gauge with ±0.5% full-scale accuracy, an IP67 case, a backlit display with bar graph, and nine engineering units plus one custom unit.
View This GaugeAshcroft K1 Pressure Transducer, 100 psi, 4-20 mA (68440-36)
Sold as a transducer, but with a 4-20 mA output it works as a transmitter. ±1.0% of span accuracy, response under 5 ms, 10 to 36 VDC supply, 17-4PH stainless diaphragm and NEMA 4X housing.
View This TransducerWIKA A-10 Pressure Transmitter, 0 to 100 psi, 4-20 mA
A compact general-purpose transmitter with a 4-20 mA output and DIN 43650 plug connector. Its all-stainless welded measuring cell has no soft seals to age, and non-linearity is under ±0.5% BFSL (non-linearity is one part of the accuracy spec, not the total error). Ranges in the series run up to 10,000 psi.
View This TransmitterWIKA S-20 Pressure Transmitter, 0 to 500 psi
A heavier-duty process transmitter with ±0.5% full-scale accuracy, 4-20 mA output, an IP65 rating and a 1/2" NPT process connection. Built for shock, vibration and aggressive media.
View This TransmitterAshcroft Watertight Pressure Switch, 100 psig
A general-purpose switch for industrial and OEM duty. The enclosure meets NEMA 3, 4, 4X, 13 and IP66, deadband is fixed or limited-adjustable depending on the switch element, and it carries UL, CSA and FM approvals.
View This SwitchAshcroft Explosion-Proof Pressure Switch, 10" WC
A low-pressure switch (10" WC, about 2,491 Pa) with ATEX and IECEx approvals for hazardous areas and a 1/4" female NPT connection. Set point and deadband are fixed at the factory, so they cannot be knocked out of adjustment in the field.
View This SwitchAshcroft Low Differential Pressure Transmitter, 15 inWC
A MEMS variable-capacitance sensor and 4-20 mA output for room pressure, building pressure, filter and fume hood monitoring. The field-adjustable LCD shows inWC, Pa or mbar.
View This TransmitterAshcroft 2½" Differential Pressure Gauge, 0 to 15 psid
A no-power differential gauge for filters, leak monitoring, flow and tank level, with a magnetic rack-and-pinion movement and ±2% full-scale accuracy (ascending). Glycerin-filled versions suit high-vibration spots.
View This GaugeMore Pressure Measurement Guides
kPa To PSI Converter And Chart
Convert between kPa, psi, bar, mbar, inH₂O and more, with a free converter and gauge vs absolute explained.
Open The ConverterWhat Is A Manometer?
U-tube, inclined, digital and capacitance manometers, how they work and how to read one correctly.
Read The Manometer GuideFlow Meter Guide
How flow meters work, including differential pressure flow measurement, and how to choose one.
Read The Flow Meter GuidePressure Gauge, Transducer, Transmitter And Switch FAQs
What Is The Difference Between A Pressure Transducer And A Pressure Transmitter?
By the most common convention, a transducer gives a small millivolt signal (mV/V) that needs amplifying, while a transmitter gives an amplified voltage or a 4-20 mA current. Manufacturers do not all follow this, so check the output on the datasheet rather than the product name.
What Is The Difference Between A Pressure Sensor And A Pressure Transducer?
"Pressure sensor" is the broad term for anything that detects pressure electronically. Strictly, the sensor is the sensing element (a strain gauge, piezoresistive chip or capacitive cell) and the transducer is the packaged device that turns its response into a usable signal. In everyday use the terms overlap heavily.
Is A Pressure Switch The Same As A Pressure Sensor?
No. A sensor or transmitter reports how much pressure there is. A switch only reports whether pressure is above or below a set point, by opening or closing a contact. Some electronic switches do both, with a display and a switching output.
What Does 4-20 mA Mean On A Pressure Transmitter?
The loop current runs from 4 mA at the bottom of the range to 20 mA at the top, so 12 mA is 50 psi on a 0 to 100 psi transmitter. A reading of 0 mA means a fault, not zero pressure.
What Is Deadband On A Pressure Switch?
The gap between the trip pressure and the reset pressure. A switch that trips at 80 psi rising with a 10 psi deadband resets at 70 psi, which stops the contact chattering when pressure hovers near the set point.
Can A Pressure Transmitter Replace A Pressure Gauge?
It can replace the measurement but not the local reading, unless it has a display. Many sites keep a mechanical gauge next to the transmitter so operators can see pressure at the point of use, and so there is a reading even if power or the control system is down.
How Accurate Is A Pressure Gauge?
It depends on the grade, and is often quoted as a percentage of full scale. A ±0.5% full-scale gauge with a 0 to 300 psi range can be out by up to ±1.5 psi anywhere on the dial, so it is most accurate, as a share of the reading, in the upper part of its range.
How Do You Calibrate A Pressure Transmitter?
Apply known pressures from a reference (a deadweight tester or a calibrated reference gauge with a pressure source) at several points across the range, usually 0, 25, 50, 75 and 100%, rising and then falling. Record the output at each point, compare it with the expected current or voltage, and adjust zero and span if the transmitter allows it.